The ACB E2.2H is a 3P circuit breaker with a rated current (In) of 2000 A. It has an Icu rating of 100 kA at 415 VAC, indicating its ability to interrupt short-circuit currents. The rated short-time withstand current, Icw (1s), is 85 kA. This circuit breaker features a withdrawable auto EKIP touch LSIG trip unit, which provides protection against overload, short circuit, and ground fault conditions. It also includes a motor operator that operates on both 48 VAC and 48 VDC power sources. The ACB E2.2H is a complete package that includes the WMP+FP+MOP components necessary for its operation.