The ACB E1.2N is a 3P circuit breaker with a rated current (In) of 1000 A. It has an Icu rating of 66 kA at 415 VAC, indicating its ability to interrupt short-circuit currents. The circuit breaker also has a rated short-time withstand current, Icw (1s), of 50 kA. The ACB E1.2N features a withdrawable auto EKIP touch LSIG trip unit, which provides protection against overload, short circuit, and ground fault conditions. It is equipped with a motor operator that operates on 380-415 VAC power supply. This complete package includes the WMP+FP+MOP components necessary for the operation of the circuit breaker.