Products

ABB 1SDA067834R1 Moulded Case Circuit Breaker 690VAC 25A 4-P 50kA Ekip Dip LSI 450A Front For: XT2S

Product Code: 1SDA067834R1

  • MCCB with 25A rated current
  • 50kA breaking capacity, 4 poles
  • Ekip Dip LSI trip unit
  • Front connection, bolt terminals
  • Complies with IEC60947-2 standards
In Stock Low Stock Out Of Stock Please See Attributes
1

Specifications

General

Product Type
Automatic Circuit Breaker
Brand
ABB
Series
SACE Tmax XT
Application
Power Distribution

Electrical

AC Power Loss Per Pole at In
0.8W
Max. Rated Operation AC Voltage (Ue)
690V AC
Position of Connection for Main Current Circuit
Front
Rated Insulation Voltage (Ui)
1000V
Type of Protection Trip Unit
EL
Rated Current (In)
25A
Rated Frequency
50/60Hz
Trip Curve
Ekip Dip LS/I
Terminal Type
Bolt
Electrical Life
8000 cycles
Mechanical Life
25000 cycles
No. of Poles
4P

Dimensions & Physical Data

Depth
82.5mm
Height
130mm
Weight
1.6kg
Width
120mm

Safety, Standards & Compliance

Standards and Approvals
IEC 60947-2

Other

Rated Ultimate Short Circuit Breaking Capacity (Icu) at 415 V, 50 Hz
50kA
Rated Service Short Circuit Breaking Capacity, (Ics) 690V AC
12kA
Rated Ultimate Short Circuit Breaking Capacity, (Icu) 690V AC
12kA
Products to compare:
Comparing Products