ABB 1SDA067582R1 Moulded Case Circuit Breaker 690/500VAC/VDC 125A 4-P 50kA TMA 625-1250A Front For: XT2S

Product Code: 1SDA067582R1

  • Rated current of 125 A for reliable performance
  • High breaking capacity of 50 kA
  • Front connection with bolt terminals
  • Compact width of 120 mm, easy to install
  • Meets IEC60947-2 standards for safety
In Stock Low Stock Out Of Stock Please See Attributes
1

Specifications

General

Product Type
Automatic Circuit Breaker
Brand
ABB
Series
SACE Tmax XT
Application
Power Distribution

Electrical

AC Power Loss Per Pole at In
11.4W
Long Time Overload Protection Adjustment Range
87.5 to 125 A
Max. Rated Operation AC Voltage (Ue)
690V AC
Position of Connection for Main Current Circuit
Front
Rated Insulation Voltage (Ui)
1000V
Type of Protection Trip Unit
TM
Rated Current (In)
125A
Rated Frequency
50/60Hz
Trip Curve
TMA
Terminal Type
Bolt
Electrical Life
8000 cycles
Mechanical Life
25000 cycles
No. of Poles
4P

Dimensions & Physical Data

Depth
82.5mm
Height
130mm
Weight
1.45kg
Width
120mm

Safety, Standards & Compliance

Standards and Approvals
IEC 60947-2

Other

Rated Ultimate Short Circuit Breaking Capacity (Icu) at 415 V, 50 Hz
50kA
Rated Service Short Circuit Breaking Capacity, (Ics) 690V AC
12kA
Rated Ultimate Short Circuit Breaking Capacity, (Icu) 690V AC
12kA