ABB 1SDA067042R1 Moulded Case Circuit Breaker 690/500VAC/VDC 125A 4-P 36kA TMA 625-1250A Front For: XT2N

Product Code: 1SDA067042R1

  • MCCB with 125 A rated current
  • Handles up to 36 kA breaking capacity
  • Rated voltage of 690/500 VAC/VDC
  • Front connection with bolt terminals
  • Compliant with IEC60947-2 standards
In Stock Low Stock Out Of Stock Please See Attributes
1

Specifications

General

Product Type
MCCB
Brand
ABB
Series
XT2N
Application
Power distribution systems , Motor protection applications, Generator protection and control systems, Commercial & industrial facilities

Electrical

Instantaneous Protection Adjustment Range
5...10xIn
Long Time Overload Protection Adjustment Range
0.7...1xIn
Max. Rated Operation AC Voltage (Ue)
690V
Type of Protection Trip Unit
TMA
Frame Size Rating
XT2 (160 frme)
Rated Current (In)
125A
Rated Frequency
50Hz to 60Hz
Trip Curve
Adj:Thermal, Adj:Magnetic
Electrical Life
8000
No. of Poles
4P

Mechanical

Frame Size
XT2 (160 frme)
Housing Material
Thermoset insulating material (moulded case)

Dimensions & Physical Data

Depth
82.5mm
Height
130mm
Weight
2.82kg
Width
120mm

Environmental

Rated Surrounding Temperature Without Derating
40°C
Pollution Degree
3
Storage Temperature
-40°C and +70°C
Operating Temperature
-25°C and +70°C
IP Rating
IP20

Safety, Standards & Compliance

Standards and Approvals
IEC 60947-2

Other

Rated Service Short Circuit Breaking Capacity (Ics) at 400 V, 50 Hz
100% of Icu
Rated Ultimate Short Circuit Breaking Capacity (Icu) at 415 V, 50 Hz
36kA